Mobile Vaporiser / Interting System
Application
- to render inert chemical warehouses, nuclear reactors, the holds of tankers, pipelines, coal mines, silos, etc. to eliminate or reduce the risk of fire and explosion
- as a temporary source of gas during a plant outage or pipeline shutdown
- to set up a gas delivery system at short notice and wherever it is needed independent of any gas supply infrastructure
Design Features
- Compact, self-sustained system inside a container frame mounted on a container chassis
- simple operation and low-maintenance
- superior reliability
- automatic power regulation
Technical Data
Medium/media | nitrogen |
Heat carrier | water |
Energy supply | heating by integrated oil- or gas-fired 0.25 to 1.4 MW boiler oil storage tank, if necessary hot-water circuit with circulation pump |
Evaporator inlet temperature |
heat carrier: +15°C to +70°C medium: -196°C to -170°C |
Evaporator outlet temperature |
heat carrier: 2°C to 5°C below inlet temperature medium: 0°C to +25°C |
Max. operating pressure | heat carrier: 2 bar medium: 25 bar |
Throughput | heat transfer medium: 100 / 200 m3/h medium: 2000 to 10000 Nm3/h |
Dimensions | corresponding to 10-ft or 20-ft container |
Weight | 3 to 5 metric tons depending on dimensions and equipment |
Connections | Flange EN 1092-1 |
Materials | 1.4541, 1.4571, SF-Cu |